STOPPING PROCEDURE
1.
Remove the AC electrical load from the generator and allow the generator
to
run
for
3
to
5 minutes
to
sta-
bilize its operating temperatures.
2.
Depress the STOP switch and hold it until the generator is completely stopped.
3.
Now
release the STOP switch.
Break-In
Precautions
Because the generator set operates at 1800 rpm
to
produce 60 Hertz,
or
at 1500
rpm
to
produce 50 Hertz,
control of the generator's engine break-in is governed
by
the current
drawn
from the generator.
DO
NOT
attempt
to
break-in
your
generator set
by
running it without a load.
Upon starting the generator set, check
for
proper operation. For the first 10 hours of the generator's opera-
tion, run the generator set between
20 and 60 percent of full-load.
After the first 10 hours
of
the generator's operation, the load may be increased
to
the rated full-load output.
Periodically vary the load.
Avoid overload at all times. An overload is signalled
by
a smoky exhaust, with reduced
output
voltage and
frequency. Monitor
the
current being drawn from the generator and keep it within the generator's rating.
Be aware of
motor
starting
loads
and the high current draw required
for
starting
motors
(see page 64
for
an
"Amps
for
Starting" chart).
Starting
Under
Normal
Conditions
Follow the procedure
below
for
routine starting of the generator:
Check the engine's
lubricating oil level prior
to
each
day's
use. Add oil as needed and maintain the oil level
at the high mark on the dipstick.
Check the
coolant level in the plastic recovery tank.
NOTE: Excessive loss
of
fresh water coolant from the plastic recovery tank indicates a
cool-
ing system leak. Check the entire cooling system; pressurize the system
to
locate the leak.
In
cases
of
excessive coolant loss, the system must be refilled as outlined under the
"PREPARATIONS FOR STARTING" section of this manual, page 33.
Visually examine the unit;
look
for
any
abnormalities and correct them as needed.
Check
to
make sure there is sufficient fuel
in
the tank and examine the filter/separator bowls
lor
contaminants.
Clean and drain the bowls as needed.
Start the generator, following the procedure outlined in the "STARTING PROCEDURES" section, page 34,
and
allow the engine's operating temperature
to
reach 130
-150'
F (55 -
66'
C) before placing the generator
under a heavy
load.
Westerbeke
Generators
36