ENGINE
TROUBLESHOOTING
The
tables
which
follow
indicate troubleshooting procedures
based upon certain problem indicators,
the
probable
causes
of
the
problems,
and
the
recommendations
to
overcome
these
problems.
Problem
Probable
Cause
Key
switch
on,
PREHEAT
switch
1.
Battery
Switch
not
on.
depressed:
no
panel
indications;
fuel
solenoid
or
electrical
fuel
pump
2.
Emergency
stop
switch
off.
2.
25-Amp
circuit
breaker
tripped.
3.
10-Amp
breaker
tripped
on
preheat
solenoid.
4.
Loose
battery
connections.
5.
Preheat
solenoid
not
operating.
START
SWITCH
DEPRESSED,
no
starter
1.
Connection
to
solenoid
faulty.
engagement.
2.
Faulty
switch.
3.
Faulty
solenoid.
4.
Loose
battery
connections.
5.
Low
batte
ry.
Note:
The
engine's electrical system
is
protected by a 25
amp
manual
reset
circuit breaker located
on
a bracket at
the
rear
of
the
engine.
The
preheat solenoid
is
close
by,
as
is
the
emergency
STOP
switch,
which
may
be
mounted
on
the
same
bracket or
on
the
back
of
the
instrument
panel,
depending
upon
the
generator
model.
Verification/Remedy
1.
Check
switch
and/or
battery
connections.
2.
Check
emergency
stop
switc~
position.
2.
Reset
breaker;
if
breaker
trips
again,
check
preheat
solenoid
circuit
and
check
circuit
for
shorts
to
ground.
3.
Check
voltage
at
and
after
breaker
on
preheat
solenoid.
4.
Check
(+)
connection
to
starter
solenoid
and
(-)
connection
to
engine
ground
stud.
Check
battery
cable
connections.
5.
Check
solenoid
"S"
terminal
for
voltage.
1.
Check
connection.
2,
Check
switch
with
ohmmeter.
3.
Check
that
12
volts
are
present
at
the
solenoid
connection.
4.
Check
battery
connections.
5.
Check
battery
charge
state.
START
switch
is
depressed;
panel
1.
Poor
connections
to
fuel
solenoid.
1.
Check
connections.
indications
OK;
starter
solenoid
OK
fuel
solenoid
not
functioning.
2.
Defective
fuel
solenoid.
2.
Check
that
12
volts
are
present
at
the
(+)
connection
on
the
fuel
run
solenoid.
Generator
engine
cranks,
but
does
not
1.
Faulty
fueling
system.
1.
Check
that
fuel
valves
are
open.
start,
fuel
solenoid
energized.
la.
Switch
to
combine
house
and
start
batteries.
1
b.
Replace
batteries.
2c.
Check
fuel
lift
pump.
2.
Preheat
solenoid
faulty.
2.
Check
solenoid.
Engine
can't
be
stopped.
1.
Faulty
DC
alternator.
1.
Remove
"Rn
connection
at
alternator,
repair
alternator.
Battery
rllns
down.
1.
Oil
Pressure
switch.
1.
Observe
if
gauges
and
panel
lights
are
activated
when
engine
is
not
running.
Test
the
oil
pressure
switch.
2.
High
resistance
leak
to
ground.
2.
Check
wiring.
Insert
sensitive
(0
-
.25
amp)
meter
in
battery
lines.
(Do
not
start
engine.)
Remove
connections
and
replace
after
short
is
located.
3.
Low
resistance
leak.
3.
Check
all
wires
for
temperature
rise
to
locate
the
fault.
4.
Poor
battery
connections.
4.
Check
cable
connections
at
battery
for
loose
connections,
corrosion
Battery
not
charging
1.
DC
charge
circuit
faulty.
1.
Perform
D.C.
voltage
check
of
generator
charging
circuit.
See
Testing
the
Battery
Charging
Circuit
in
this
manual.
Generator
engine
stops.
1.
Fuel
lift
pump
failure.
1.
Fuel
lift
pump
should
make
a
distinct
ticking
sound.
Replace
pump
with
spare.
2.
Switches
and/or
wiring
loose
2.
Inspect
wiring
for
short
circuits
and
loose
connections.
or
disconnected.
Inspect
switches
for
proper
operation.
3.
Fuel
starvation.
3.
Check
fuel
supply,
fuel
valves,
fuel
lift
pump.
4.
25
Amp
circuit
breaker
tripping.
4.
Check
for
high
DC
amperage
draw
during
operation.
Ensure
breaker
is
not
overly
sensitive
to
heat
which
would
cause
tripping.
5.
Exhaust
system
is
restricted.
5.
Check
for
blockage,
collapsed
hose,
carbon
buildup
at
exhaust
elbow.
6.
Water
in
fuel.
6.
Pump
water
from
fuel
tank(s);
change
filters
and
bleed
fuel
system.